Siemens S7 communication

Read and write SIMATIC controllers over their built-in Ethernet port with the S7 protocol, without an extra gateway, OPC server or PLC programming.

  • s7

PLCGateway speaks the S7 protocol (ISO-on-TCP, port 102) that every SIMATIC CPU with an Ethernet interface understands. Data blocks, markers, inputs, outputs and S7 strings are read directly, nearby areas are merged and fetched in optimised multi-item requests sized to the PDU of the CPU.

For S7-1200 and S7-1500, enable PUT/GET access and switch off optimised block access for the data blocks you read. Controllers with their own OPC UA server can be connected through the OPC UA client as well; PLCGateway then works with symbolic names.

Driver id
s7
Connection
ISO-on-TCP (RFC 1006) · TCP 102
Address browsing
addresses are typed or imported
Writing
yes

What PLCGateway reads and writes

  • Data blocks: bits, bytes, words, double words, REAL, LREAL
  • Markers (M), inputs (I / E) and outputs (Q / A)
  • S7 STRING with its two-byte header, or raw character arrays
  • Timers and counters of classic CPUs
  • Writing of single values from screens, OPC UA, MQTT or MCP
  • Rack / slot and TSAP settings for S7-300/400, S7-1200/1500 and LOGO!

Address examples

AddressMeaning
DB1.DBX0.3Data block 1, byte 0, bit 3
DB1.DBW2 · DB1.DBD4Word / double word (width from the tag type)
DB10.DBS20[32]S7 STRING with a capacity of 32 characters
MW100 · M10.3Marker word / marker bit
I0.0 · IW2Input bit / input word
Q4.1 · QW2Output bit / output word

Controllers and devices

Equipment that is typically connected with this driver.

Connect in a few steps

  1. In TIA Portal allow PUT/GET communication and switch off optimised block access for the data blocks to read (S7-1200 / S7-1500).

  2. Add an S7 device with the IP address; rack 0, slot 1 for S7-1200/1500, rack 0, slot 2 for S7-300/400, or the TSAP for LOGO!.

  3. Enter the tags with their addresses or import them from CSV and test the connection.

  4. Use the values in SCADA screens or share them over OPC UA with MES, ERP and cloud systems.

Questions and answers

Do I have to change the PLC program?

No. Only the CPU properties change: PUT/GET access and, for data blocks, optimised block access off. The program logic stays as it is.

Which is better for an S7-1500: S7 or OPC UA?

Both work. The S7 driver needs no OPC UA licence on the CPU and is very fast; the OPC UA client uses the symbolic names and the security of the CPU's OPC UA server. Many sites use S7 for fast cyclic values and OPC UA where symbolic access matters.

Is LOGO! supported?

Yes. LOGO! 0BA7 and LOGO! 8 are connected with the S7 driver using the TSAP configured in LOGO!Soft Comfort.

Connect your machines

Tell us which controllers you run; we show you PLCGateway with your own addresses.